Product Description
Wiring for controlling electrical equipment and instrument meters, monitoring and controlling return circuit, protecting and measuring in power distribution with rated voltage up to 450/750V(0.6/1KV) A.C.
GB/T9330-2008 ,IEC 60502, etc.
*We can also design and produce for special application requirement.
1. The maximum permissible continuous operating temperature is 70℃
2. The lowest installation temperature of the cable is 0℃ .
3. Permissible Min. Bending radius not less than 6 times of the completed cable diameter for unarmoured cable; not less than 12 times of the completed cable diameter for armoured or copper tape screened cable; not less than 6 times of the completed cable diameter for screened flexible cable.
Chinese Type |
Descriptions |
Applications |
KVV |
Copper conductor PVC insulated |
For laying indoor, in tunnels, ducts, |
KVVR |
Copper conductor PVC insulated and sheathed |
For laying indoor, in tunnels, ducts and movable using |
KVVP |
Copper conductor PVC insulated and sheathed |
|
KVVRP |
Copper conductor PVC insulated and sheathed copper |
For laying indoor, in tunnels, ducts and flexible and shield |
KVVP2 |
Copper conductor PVC insulated |
For laying indoor, in tunnels, ducts, conduit etc. |
KVVP2-22 |
Copper conductor PVC Insulated |
Used in light-current control system and heavy-current |
KVV22 |
Copper conductor PVC insulated |
For laying indoor, in tunnels, ducts, conduit and direct burial |
KVV32 |
Copper conductor PVC insulated |
For laying indoor, in tunnels, ducts, conduit and direct burial |
Type |
Rated voltage |
Nominal conductor cross section (m㎡) |
Standards |
|||||||
0.75 |
1.0 |
1.5 |
2.5 |
4 |
6 |
10 |
|
|||
Number of cores |
|
|||||||||
KVV |
450/750V |
2~61 |
2~14 |
2~10 |
GB/T9330-2008 |
|||||
KVVR KVVRP |
2~61 |
- |
- |
|||||||
KVVP2 KVVP |
4~61 |
4~14 |
4~10 |
|||||||
KVV22,KVV32, KVVP2-22 |
7~61 |
4~61 |
4~14 |
4~10 |
Note: Recommended core numbers are 2, 3, 4, 5, 7, 8, 10, 12, 14, 49, 24, 27, 30, 37 and 61